Current ratings for HO7-RNF for current supply in industrial application
Operating temperature at conductor 60C ambient temperature 30C
Number of cores | 1 core | 2 cores | 3 cores | 3 cores | 4 cores | 5 cores | |
Number of loaded cores | 2 cores loaded | 3 cores 1oaded | 2 cores loaded | 2 cores loaded | 3 cores loaded | 3 cores loaded | 3 cores loaded |
Cross section mm2 | Current ratings in ampere(A) | ||||||
4.0 | 34 | 30 | 34 | 35 | 29 | 30 | 30 |
6.0 | 43 | 38 | 43 | 44 | 36 | 37 | 38 |
10.0 | 60 | 53 | 60 | 62 | 51 | 52 | 54 |
16.0 | 79 | 71 | 79 | 82 | 67 | 69 | 71 |
25.0 | 104 | 94 | 105 | 109 | 89 | 92 | 94 |
35.0 | 129 | 117 | 135 | 110 | 114 | ||
50.0 | 162 | 148 | 169 | 138 | 143 | ||
70.0 | 202 | 185 | 211 | 172 | 178 | ||
95.0 | 240 | 222 | 250 | 204 | 210 | ||
120.0 | 280 | 260 | 292 | 238 | 246 | ||
150.0 | 321 | 300 | 335 | 273 | 282 | ||
185.0 | 363 | 341 | 378 | 309 | 319 | ||
240.0 | 433 | 407 | 447 | 365 | 377 | ||
300.0 | 497 | 468 | 509 | 415 | 430 | ||
400.0 | 586 | 553 | |||||
500.0 | 670 | 634 | |||||
630.0 | 784 | 742 |
For the method of installation
Single core cables are bunched (unit form). 2 cores cables laid parallel with contact .3 cores cables are in triangle-form
Conversion factors for deviating ambient temperature
Ambient temperatureat air 30C | 30 | 35 | 40 | 45 | 50 | 55 |
Factor | 1.0 | 0.91 | 0.82 | 0.71 | 0.58 | 0.41 |
HO7RN-F: voltage drop (per ampere per meter)
Conductor Size(mm) | 1 Two Core or 2 Single Core Cables DC(mV/A/m) | Two Core Cable Single Phase AC (mV/A/m) | 1 Three Core, Four Core or Five Core Cable Single Phase AC (mV/A/m) | 2 Single Core Cables Touching Single Phase AC* mV/A/m | ||||||
---|---|---|---|---|---|---|---|---|---|---|
1.0 | - | - | - | - | ||||||
1.5 | 30.6 | 30.6 | 26.5 | 26.50 | ||||||
2.5 | 19.0 | 19.0 | 16.4 | 16.40 | ||||||
4.0 | 13.0 | 13.0 | 11.0 | 10.20 | ||||||
6.0 | 8.4 | 8.4 | 7.3 | 6.75 | ||||||
10.0 | 5.0 | 5.0 | 4.3 | 4.00 | ||||||
16.0 | 3.1 | 3.1 | 2.7 | 2.52 | ||||||
r | x | z | r | x | z | r | x | z | ||
25.0 | 2.000 | 2.00 | 0.175 | 2.00 | 1.700 | 0.150 | 1.700 | - | - | - |
35.0 | 1.420 | - | - | - | 1.200 | 0.150 | 1.200 | 1.420 | 0.210 | 1.430 |
50.0 | 0.990 | - | - | - | 0.900 | 0.145 | 0.910 | 0.990 | 0.210 | 1.010 |
70.0 | 0.700 | - | - | - | 0.610 | 0.140 | 0.630 | 0.700 | 0.200 | 0.720 |
95.0 | 0.530 | - | - | - | 0.460 | 0.135 | 0.480 | 0.530 | 0.195 | 0.560 |
120.0 | 0.410 | - | - | - | 0.360 | 0.135 | 0.390 | 0.410 | 0.190 | 0.460 |
150.0 | 0.330 | - | - | - | 0.290 | 0.130 | 0.320 | 0.330 | 0.190 | 0.380 |
185.0 | 0.270 | - | - | - | 0.240 | 0.130 | 0.270 | 0.270 | 0.190 | 0.330 |
240.0 | 0.210 | - | - | - | 0.185 | 0.130 | 0.220 | 0.210 | 0.185 | 0.280 |
300.0 | 0.165 | - | - | - | 0.145 | 0.125 | 0.195 | 0.170 | 0.180 | 0.250 |
400.0 | 0.125 | - | - | - | - | - | - | 0.130 | 0.175 | 0.220 |
630.0 | 0.073 | - | - | - | - | - | - | 0.084 | 0.170 | 0.190 |
Conductor operating temperature: 85oc
1. The voltage drop figures given above are based on a conductor operating temperature of 85oc and are therefore not accurate when the operating temperature is in excess of 85oc
2. * A larger voltage drop will result if the cables are spaced
The above table is in accordance with Table 4H2B of the 16th Edition of IEE Wiring Regulations
For cables having conductors of 16mm or less cross-sectional area their inductance can be ignored and (mV/A/m)r values only tabulated. For cables having conductors greater than 16mm the impedence values are given as (mV/A/m)z, together with the resistive component (mV/A/m)r and the reactive component (mV/A/m)x.
The above paragraph is extracted from Appendix 4 of the 16th Edition of IEE Wiring Regulations