Cross section
mm
Stranded
wires
Multistranded
Wires
Fine
Wires
Extra-fine wires
Class 2
DIN VDE 0295
Class 5
DIN VDE 0295
Class 6
DIN VDE 0295
Column 1 Column 2 Column 3 Column 4 Column 5     Column 6 Column 7
Number3)
Of wires x
single
wire Ø mm
Number
Of wires x
single
wire Ø mm
Number1)
Of wires x
Single2)
wire Ø mm
Number1)
Of wires x
Single2)
wire Ø mm
Number1)
Of wires x
single
wire Ø mm
Number1)
Of wires x
single
wire Ø mm
Number1)
Of wires x
single
wire Ø mm
0.05 14 X 0.07 26 X 0.05
0.08 40 X 0.05
0.09 24 X 0.07
0.14 18 X 0.1 18 X 0.1 18 X 0.1 36 X 0.07 72 X 0.05
0.25 14 X 0.15 32 X 0.1 32 X 0.1 65 X 0.07 128 X 0.05
0.34 7 X 0.25 19 X 0.15 42 X 0.1 42 X 0.1 88 X 0.07 174 X 0.05
0.38 7 X 0.27 12 X 0.2 21 0.15 48 X 0.1 100 X 0.07 194 X 0.05
0.5 7 X 0.30 7 X 0.30 16 X 0.2 28 X 0.15 64 X 0.1 131 X 0.07 256 X 0.05
0.75 7 X 0.37 7 X 0.37 24 X 0.2 42 X 0.15 96 X 0.1 195 X 0.07 384 X 0.05
1.0 7 X 0.43 7 X 0.43 32 X 0.2 56 X 0.15 128 X 0.1 260 X 0.07 512 X 0.05
1.5 7 X 0.52 7 X 0.52 30 X 0.25 84 X 0.15 192 X 0.1 392 X 0.07 768 X 0.05
2.5 7 X 0.67 19 X 0.41 50 X 0.25 140 X 0.15 320 X 0.1 651 X 0.07 1280 X 0.05
4.0 7 X 0.85 19 X 0.52 56 X 0.3 224 X 0.15 512 X 0.1 1040 X 0.07
6.0 7 X 1.05 19 X 0.64 84 X 0.3 192 X 0.2 768 X 0.1 1560 X 0.07
10.0 7 X 1.35 49 X 0.51 80 X 0.4 320 X 0.2 1280 X 0.1 2600 X 0.07
16.0 7 X 1.70 49 X 0.65 128 X 0.4 512 X 0.2 2048 X 0.1
25.0 7 X 2.13 84 X 0.62 200 X 0.4 800 X 0.2 3200 X 0.1
35.0 7 X 2.52 133 X 0.58 280 X 0.4 1120 X 0.2
50.0 19 X 1.83 133 X 0.69 400 X 0.4 705 X 0.3
70.0 19 X 2.17 189 X 0.69 356 X 0.5 990 X 0.3
95.0 19 X 2.52 259 X 0.69 485 X 0.5 1340 X 0.3
120.0 37 X 2.03 336 X 0.67 614 X 0.5 1690 X 0.3
150.0 37 X 2.27 392 X 0.69 765 X 0.5 2123 X 0.3
185.0 37 X 2.52 494 X 0.69 944 X 0.5 1470 X 0.4
240.0 61 X 2.24 627 X 0.70 1225 X 0.5 1905 X 0.4
300.0 61 X 2.50 790 X 0.70 1530 X 0.5 2385 X 0.4
400.0 61 X 2.89 2035 X 0.5
500.0 61 X 3.23 1768 X 0.6
630.0 91 X 2.97 2228 X 0.6

1) The number of individual wires are without obligation.
2) The diameters of the single wires for each conductor are not allowed to exceed the values stated to DIN VDE 0295. The single wires of stranded conductor must have all the same nominal diameters.
3) Minimum-number of single wires of stranded conductor. The single wires of stranded conductor must have all the same nominal diameters.

2) Note: permissible maximum diameter of single wires:

nominal value mm maximum value mm
0.2 0.21
0.25 0.26
0.3 0.31
0.4 0.41
0.5 0.51
0.6 0.61

AMERICAN WIRE GAUGE (AWG) TO METRIC CONVERSION

 

AWG Cross Section (mm) Stranding ResistanceW/km AWG Cross Section (mm) Stranding ResistanceW/km
38 0.008 1 x 0.10 2125 18 0.90 7 x 0.40 19.2
38 0.009 7 x 0.04 1930 18 0.96 19 x 0.25 17.9
36 0.013 1 x 0.12 1360 16 1.30 1 x 1.29 13.2
36 0.014 7 X 0.05 1217 16 1.23 19 X 0.28 14.0
34 0.020 1 x 0.16 856 14 2.08 1 x 1.62 8.28
34 0.022 7 x 0.06 777 14 1.94 19 x 0.36 8.86
32 0.032 1 x 0.20 538 12 3.31 1 x 2.05 5.20
32 0.034 7 x 0.08 538 12 3.08 19 x 0.45 5.58
32 0.035 19 x 0.05 446 10 5.26 1 x 2.58 3.28
30 0.051 1 x 0.25 338 10 5.26 19 x 0.6 3.28
30 0.057 7 x 0.10 338 8 8.38 1 x 3.26 2.06
30 0.059 19 x 0.06 286 8 8.35 19 x 0.75 2.06
28 0.080 1 x 0.32 213 6 13.29 1 x 4.11 1.59
28 0.089 7 x 0.12 213 6 13.29 19 x 0.96 1.59
28 0.090 19 x 0.08 186 4 21.15 1 x 5.18 0.815
26 0.128 1 x 0.40 134 4 21.14 19 x 1.19 0.815
26 0.141 7 x 0.16 122 2 33.63 1 x 6.54 0.513
26 0.155 19 x 0.10 113 2 33.61 19 x 1.50 0.513
24 0.205 1 x 0.51 84 1 42.41 1 x 7.34 0.424
24 0.227 7 x 0.20 76 1 42.38 19 x 1.68 0.424
24 0.241 19 x 0.12 69 1/0 53.40 19 x 1.89 0.253
22 0.324 1 x 0.64 53 2/0 67.40 19 x 2.17 0.291
22 0.355 7 x 0.25 48 4/0 107 19 x 2.68 0.182
22 0.382 19 x 0.16 45 250 MCM 127 37 x 2.09 0.139
20 0.519 1 x 0.81 33 300 MCM 152 37 x 2.29 0.119
20 0.563 7 x 0.32 30.40 350 MCM 177 37 x 2.47 0.102
20 0.616 19 x 0.20 28.30 400 MCM 202 37 x 2.64 0.091
18 0.785 16 x 0.25 21.20 500 MCM 253 37 x 2.95 0.072
18 0.823 1 x 1.02 20.90        

The cross reference list shows equivalent nominal values. Actual cross sections may vary. The AWG values are approximate if the cables Are made to European Standards mm 2 and vise versa. In critical applications, where the current reaches upper limits. The deviating Operation conditions for installation and laying according to standards are to be taken into consideration.